Data Center Overall: 54,142 sq. ft. Raised Floor: 3,397 sq. ft. Office Space: Customer area Site Area: Light industrial Seismic Zone: Low Built: 2009
Types: Cage, locking cabinets Standard Rack: 42U Raised Floor Load: 8 KPA Sub Floor Load: Cross Connect: Copper, fiber, coaxial Remote Hands: 24x7 Loading Dock: Yes
Electrical Capacity 132 w/sq. ft. Cabinet (2.4, 4.3 & 6.2 Kw) UPS Configuration: 2N # Utility Feeders: 2 Standby Power Config: 2N Standby Power: Four 1500 Kva diesel generators, 24 hrs of fuel at full load stored at site in storage tanks
HVAC Distribution: Chilled water cooled CRAC’s HVAC System: N+1 Chillers: Eight chillers
Fire Alarm: VESDA (air sampling) smoke detection & alarm system Fire Suppression Data Center Areas: Water mist system Non-Equipment Areas: Wet sprinkler