Data Center Overall: 62,516 sq. ft. Raised Floor: 33,155 sq. ft. Office Space: Customer Drop in Cubicles Site: 2-story Site Area: Industrial Park Seismic Zone: 4 Built: 1967, 1970, 2000 Retrofitted: 2013
Types: Cage, locking cabinets Standard Rack: 42U Raised Floor Load: 150 lbs. / sq. ft. Sub Floor Load: 300 lbs. / sq. ft. Cross Connect: Copper, fiber, coaxial Remote Hands: 24x7 Loading Dock: Yes
Electrical Capacity 120 w/sq. ft. Cabinet (2.4, 4.3 & 6.2 Kw) UPS Configuration: 2N # Utility Feeders: 1 Standby Power Config: N+1 Standby Power: Three 1500 KW diesel generators & Two 750 KW Solar turbine generators, two underground 8,000-gallon fuel oil storage tanks, and one above ground 8,000 gallon fuel oil storage tank
HVAC Distribution: N+1 HVAC System: N+1 Chillers: Two 800 Chillers/CoolingTower & 2-200 Ton Chiller/ Cooling Towers w/ 2-30,000 gal onsite make-up water tanks
Fire Alarm: VESDA Smoke Detection and Conventional Addressable Fire Alarm System Fire Suppression Data Center Areas: Pre-action dry pipe Non-Equipment Areas: Wet sprinkler