Data Center Overall: 140,654 sq. ft.
Colocation: 92,320 sq. ft.
Office Space: Customer drop in cubicles
Site Area: Business park
Types: Cage, locking cabinets
Standard Rack: 45U 42" deep 4 & 6 kW
Raised Floor Load: 300 lbs. / sq. ft.
Sub Floor Load: 300 lbs. / sq. ft.
Cross Connect: Copper, fiber, coaxial
Remote Hands: 24x7
Electrical Capacity
Phase I & II - 120 w/sq. ft.
Phase III & IV - 200 w/sq. ft.
Cabinet (2.4, 4.3 & 6.2 Kw)
UPS Configuration: N+1
# Utility Feeders: 2
Standby Power Config: N+1
Standby Power: Six 2,000 Kw diesel generators, five belly tanks and one standalone.
HVAC Distribution:
N+1 HVAC System: N+1
Chillers: Eight 400 ton air-cooled chillers. Closed chill water loop with municipal makeup water.
Fire Alarm:
VESDA smoke detection and conventional addressable fire alarm system Fire Suppression
Data Center Areas: Pre-action dry pipe Non-Equipment Areas: Dry pipe